Home » Product List » Low Volts PVC Fixed Wiring & Mains Cables » Building Wire
Product Details
Building Wire
| Packing: | 100m in Rings or on Spools,or in Cardboard Boxes. |
|---|---|
| Model NO.: | H05V-R |
| Standard: | 0.5~1mm2 |
| Productivity: | 100, 000 Meters/Week |
| Unit Price: | US $ 0.15-12.85/ Meter |
| Shipment Terms: | CFR |
| Payment Terms: | L/C,T/T |
| Minimum Order: | 1000 Meter |
| Price Valid Time: | From Dec 14,2011 To Dec 13,2012 |
| HS Code: | 854460 |
| Trademark: | JIQING & OEM |
| Origin: | Guangdong, China |
| Insulation Material: | PVC |
| Conductor Type: | Stranded |
| Conductor Material: | Copper |
| Application: | General Purpose Using |
| Type: | Insulated |
| Volts Grade: | 300/500V |
| Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
Product Description
Building wire
1. Voltage Rating: 300/500V
2. Conductor: Annealed copper, class 1 solid(H05V-U), class 2 stranded(H05V-R)
3. Insulation: PVC compound.
4. Maximum conductor operating temperature: +70 degree.
5. Lowest ambient temperature for fixed installation: -30 degree.
6. Lowest installation temperature: -5 degree.
7. Max. Short-circuit conductor temperature: +160 degree.
8. Test voltage 50Hz: 2000V
9. Min. Bending radius: 4X cable dia.
10. Packing: 100m In rings or on spools, or in cardboard boxes.
11. Standards: DIN VDE 0281-3, BS 6004
|
Nominal cross- sectional area of conductor |
Radial thickness of insulation |
Approx. Over. Dia. |
Approx. cable weight |
Max. resistance of conductor at 20 degree |
Min. insualtion resistance at 70 degree |
| mm2 | mm | mm | kg/km | Ohm/km | M Ohm/km |
| 0.5 | 0.6 | 2.1 | 9 | 36 | 0.014 |
| 0.75 | 0.6 | 2.3 | 12 | 24.5 | 0.012 |
| 1 | 0.6 | 2.5 | 14 | 18.1 | 0.011 |
Inquiry Basket (